Air sampling equipment
Product Details
system specifications
Model name |
VLI-885 |
---|---|
Type |
Normal
type, reuse type, air suction type, analog type, number of
air suction inputs 4, maximum air pipe distance 360m, Maximum use distance per number of air suction input 120m |
Type approval number |
Gam 73-16 |
KC certification number |
R-R-CoC-VLI-885 |
Nominal sensing concentration range |
1 ~ 5%/m |
Rated voltage |
DC 24V |
Ambient temperature/Relative humidity |
0°C ~ 39°C / 10 ~ 95% |
Current consumption |
Monitoring 415mA / Alarm 440mA |
Sensing method |
Sensing method / A method of measuring the value of light scattering in the laser chamber by sucking smoke particles through the air suction pipe |
Sensitivity range |
0.005 ~ 20% obs/m |
Color |
Black |
Size |
426.5(W) X 316.5(H) X 180(D)mm |
IP class |
66 |
Accessories |
VSP-030/VSP-033/VSP-031/VSP-036/VSP-032 |